AC/DC Multimeter Probes
CP60
CP30
CP1000

AC/DC Oscilloscope Probes
CP35
CP305
CP1005

AC/DC Clamp Meters
CP41 TRMS
CP410 TRMS
CP1010 TRMS

AC Only Current Probes
ACP200 M3
ACP1000 SM
ACP1000 SM

Manufacturer/Origin
:GMC I-PROSyS/UK

Electrical Characteristics
Nominal Current IN ............................... : 1200ARMS
Continuous Measuring Range ............... : 100mA to 1200ARMS
Overload Capability for 1 Hour, .............. : 1500ARMS (50/60Hz)
33% Duty Cycle
Output Sensitivity ................................. : 1mV/A
Turns Ratio ......................................... : 1000:1
Accuracy…(@100A, 2kHz, +25°C) ........... : ±1% of reading
Load Impedance .................................. : >10kOhm
Phase Shift at 2kHz .............................. : ±1 degree
Frequency Range ................................. : 30Hz to 10kHz (-3dB)
Working Voltage ................................... : 600V ACRMS or DC
(see Safety Standards section)

Accuracy

Primary Current 0.5 to 10A 10 to 50A 50 to 200A 200 to 1000A to 1200A
Accuracy
(of rdg)
±3% ±3% ±1.5% ±0.8% 0.5%
Phase Error Not specified 1.5° 0.75° 0.5°

General Characteristics
Maximum Conductor Size .............. : 54mm diameter
Output Connection ........................ : 4mm safety sockets
Operating Temperature Range ........ : -10 to +55°C
Storage Temperature Range ........... : -40 to +70°C
Operating Humidity ........................ : 15% to 85% (non condensing)
Weight ......................................... : 650g

Safety Standards
BSEN61010-1: 1993 and Amendment A2: July 1995
BSEN61010-2-032: 1995
BSEN61010-2-031: 1995
600VRMS, Category III, Pollution Degree 2
Use of the probe on uninsulated conductors is limited to 600 V ACRMS or DC and frequencies
below 1kHz.

EMC Standards
EN61326 :1998