Transducers/Energy Management
Angular Position Transmitter
Process Management/Signal Converter
Shunt
AC/DC Split-core Transducer
Current Probes
Energy Measurement w/ Rogowski
Power Supplies
Connectors
Communication Networks
 

 

N-biz Electronics Home > Product List > Current Probes

Current Probes


AC/DC Multimeter Probes
CP60
CP30
CP1000

AC/DC Oscilloscope Probes
CP35
CP305
CP1005

AC/DC Clamp Meters
CP41 TRMS
CP410 TRMS
CP1010 TRMS

AC Only Current Probes
ACP200 M3
ACP1000 SM
CP60

iProsys CP60

Manufacturer/Origin
:GMC I-PROSyS/UK

Electrical Characteristics
Current Ranges..............................................: 20A / 60A DC or ACPEAK
Measuring Range ..........................................: 0 to ±60A
Output Sensitivity...........................................: 100mV / 10mV / A
Resolution.....................................................: ±1mA / ±10mA
Accuracy…(20A range) ..................................: ±1% of reading ± 5mA
……………(60A range) ...................................: ±2% of reading ± 50mA
Load Impedance ............................................: > 10k Ohms and £ 100pF
Conductor Position Sensitivity .........................: ±1% relative to centre reading
Frequency Range ..........................................: DC to 50kHz (- 3dB)
Temperature Coefficient ..................................: ±0.1% of reading / °C
Power Supply.................................................: 9V Alkaline, MN1604/PP3
.....................................................................: 50 Hours, low battery indicator
Working Voltage (see Safety Standards section) .: 150V ACRMS or DC

General Characteristics
Maximum Conductor Size.............................: 12mm diameter
Output Connection......................................: 4mm safety plugs
Output Zero................................................: Auto zero via push button
Cable Length..............................................: 1.5 meters long coaxial cable
Operating Temperature Range.......................: 0 to +50 °C
Storage Temperature Range..........................: -20 to +85 °C
Operating Humidity ......................................: 15% to 85% (non condensing)
Weight.......................................................: 250 g

Safety Standards
BS EN 61010-1: 2001
BS EN 61010-2-032: 2002
BS EN 61010-031: 2002
150 VRMS, Category I, Pollution Degree 2
Use of the probe on uninsulated conductors is limited to 150 V ACRMS or DC and frequencies below 1 kHz.

EMC Standards
EN 61326-2-2:2006

Dimensions (in mm)