Angular Position Transmitter
KINAX WT717 |
|
|
Manufacturer/Origin:
CamilleBauer/Switzerlan
Sea-water resistant version
|
Programmable shaft transmitter for angular position
for heavy duty applications, > dia. 100 mm
Converts the angular position of a shaft into a load independent direct current signal,
proportional to the angular shaft position. The unit is contact free and has minimal
mechanical abrasion.
Main features
• Robust transmitter for angular position in singleturn and multiturn suitable for field applications
• Highest degree of mechanical and electrical safety
• Capacitive scanning system provides absolute position immediately after activation
• No wear, low annual maintenance and mountable anywhere
• Measuring range, sense of rotation, characteristic, switching point programmed using PC
• Adjustement / Independent fine adjustment of the analog output, zero position and measuring
range
• Simulation of measured values / The testing of the subsequent device chain is already possible
during the installation phase
• Measured value acquisition / Display of the instantaneous value and a trend graph of the
measured value on the screen
• Characteristic of the output value / Programmable as a linear, V-characteristic, or any
characteristic curve
• Small bearing play influence < 0.1%
• Available with explosion protection “Intrinsic safety” Ex ia IIC T6
• Can be mounted within the hazardous area
• Also available as sea-water resistant version |
Technical data
Measuring range: Programmable between
0 ... 10°, 0 ... 50°, 0 ... 350° (without gear)
Programmable etween
0 ... 10°, 0 ... 50°, 0 ... 350° up to max. 1600 turn (with gear)
Measuring output: 4 ... 20 mA with 2-wire connection
Output variable IA: Load-independent DC current, proportional to the input angle
Current limitation: IA max. 40 mA
Power supply: 12 ... 33 V DC (version non-intrinsically safe, without electric isolation)
12 ... 30 V DC (version intrinsically safe, without electric isolation)
Power consumption
max.: Approx. 5 mA + IA
Residual ripple
in output current: < 0.3% p.p.
Accuracy: Error limit ≤ ±0.5%
Reproducibility: < 0.2%
Response time: < 5 ms
Electrical connection: Cable glands, connection print with screw terminal
Mechanical data
Starting torque: Approx. 25 Ncm
Clearance influence: ±0.1%
Drive shaft diameter: 19 mm or 12 mm
Admissible static
loading of shaft: Max. 1000 N (radial)
Max. 500 N (axial)
Mounting position: Any
Material: Housing flange standard: steel
Housing flange sea-water: high-grade steel 1.4462
Housing cover with cable glands: aluminium
Shaft: rust-proof hardened steel
Weight: Approx. 2.9 kg (without additional gear)
Approx. 3.9 kg (with additional gear) |
|
|
|